Applications
C45LE is applicable to a line of AC 50Hz/60Hz, rated voltage 230V for single pole two-wire, 2-pole or 400V for 3-pole, 3-pole 4-wire,4-pole and rated current up to 40A. It can protect the line and motor from overload and short circuit. It can also be used for infrequent line conversion and infrequent motor start. It conforms with the standards of IEC61009.
C45LELeakage Circuit Breaker With Over-current Protection
Product description
Main technical parameter
TypeC45LE
Pole1P+N, 2P3P, 3P+N, 4P
Rated current (A)6,10,16,20,25,32,40,50,63
Rated voltage (V)230400
Rated short circuit breaking capacity Icn(KA)6-32A:6/40-63:4.5
Rated residual making/breaking capacity IAm(A)2000
Rated residual action current IAn(A)0.03,0.05,0.1,0.3
Rated residual non-action current IAno(A)30.5IΔn
Applicable conducting wire
Rated current(A)1-6A10A16,20A25A32A40,50A63A
Norminal cross section of
     wire mmp²
11.52.5461016
Residual current breaking time
ln(A)lΔn(A)Breaking time(s) when equals to rating following
lΔn2lΔn5lΔn5,10,20,50,100,200,500a(A)lΔtb
6-630.03,0.05,0.1,0.30.10.060.040.040.04
The over-current protection property
Ambient
     Temperature
Initial StatusTest CurrentExpected ResultExpected ResultNote
30± 2℃Cold position1.13lnt≤1hNon release-
Carried out immediately after
     previous test
1.45lnt<1hRelease-
Cold position2.55ln1s<t<60s
     (In ≤ 32A)
ReleaseCurrent smoothly rises to specified
     value within 5s
Cold position2.55ln1s<t<120s
     (In>32A)
Release
-5~+40℃Cold position3lnt ≤0.1sNon-releaseType B
Cold position5lnt <0.1sReleaseType B
Cold position5lnt ≤0.1sNon-releaseType C
Cold position10lnt <0.1sReleaseType C
Cold position10lnt ≤0.1sNon-releaseType D
Cold position20lnt <0.1sReleaseType D
Certification