Home > Products > CIRCUIT BREAKER > DZ47-63Mini Circuit Breaker

DZ47-63

Mini Circuit Breaker
Applications
MCB is applicable to a line of AC 50Hz,230V in single pole,400V in double, three, four poles for protecting overload and short circuit, and rated current up to 63A. It can also be used for infrequent line conversion under the normal condition. The breaker is applicable to lighting distribution system in industrial enterprise, commercially district, high-rise building and dwelling house. It conforms with the standards of IEC60898.
DZ47-63Mini Circuit Breaker
Product description
Main technical parameter
TypeMCB
Pole1P2P,3P,4P
Rated current (A)6,10,16,20,25,32,40,50,63
Rated voltage(V)230400
Ambient temperature~5℃~+40℃
Type of instantaneous releaseCDCD

Rated short circuit breaking

capacity Icn(KA)

1-32A: 6

50-63A:4.5

4.5

1-32A: 6

50-63A:4.5

4.5
Applicable conducting wire
Rated current(A)Norminal cross section of wire mm²
1-6A1
10A1.5
16,20A2.5
25A4
32A6
40,50A10
63A16
The over-current protection property
Ambient
     Temperature
Initial StatusTest CurrentExpected ResultExpected ResultNote
30 ± 2℃Cold position1.13lnt≤1hNon-release-
Carried out immediately after previous test1.45lnt<1hRelease-
Cold position2.55ln1s<t<60s (ln≤32A)ReleaseCurrent smoothly rises to specified
     value within 5s
Cold position2.55ln1s<t<120s (ln>32A)Release
-5~+40℃Cold position3lnt≤0.1sNon-releaseType B
Cold position5lnt<0.1sReleaseType B
Cold position5lnt≤0.1sNon-releaseType C
Cold position10lnt<0.1sReleaseType C
Cold position10lnt≤0.1sNon-releaseType D
Cold position20lnt<0.1sReleaseType D
Certification